# Modbus/TCP

Modbus/TCP is a communication protocol which is a variant of the Modbus family. It is based on a client/server architecture and intended for use in industrial automation especially with PLCs or IO modules. Modbus/TCP is defined in IEC 61158.

Modbus uses big-endian representation for addresses and data items.

## Protocol Structure

| Transaction identifier | Protocol identifier    | Length field | Unit identifier | Function code | Data   |
| ---------------------- | ---------------------- | ------------ | --------------- | ------------- | ------ |
| 2 byte                 | 2 byte (always 0x0000) | 2 byte (n+2) | 1 byte          | 1 byte        | n byte |

[Connection Properties](https://docs.cybus.io/1-11-0/documentation/industry-protocol-details/modbus-tcp/modbusconnection)

[Endpoint Properties](https://docs.cybus.io/1-11-0/documentation/industry-protocol-details/modbus-tcp/modbusendpoint)

## Supported Function Codes

For reading or writing data over Modbus/TCP the protocol provides a set of functions. Which action should be performed on the other end of the connection is defined by the function code (FC).

The following function codes are supported:

| Function code | Action                           | Operation |
| ------------- | -------------------------------- | --------- |
| 1             | Read coils                       | subscribe |
| 2             | Read discrete inputs             |           |
| 3             | Read holding registers           |           |
| 4             | Read input registers             |           |
| 5             | Write single coil                | write     |
| 6             | Write single holding register    |           |
| 15            | Write multiple coils             |           |
| 16            | Write multiple holding registers |           |

## Supported Data Types

In Modbus/TCP there are no predefined data types. Connectware supports sending the raw payload over MQTT as binary. If the data type is known and supported by the respective function code, the payload is converted to JSON format.

The desired data type on read or on write is specified with the property `dataType`. The possible values are as follows:

| DataType/FC | 1 | 2 | 3 | 4 | Size     |
| ----------- | - | - | - | - | -------- |
| raw         | ✓ | ✓ | ✓ | ✓ | variable |
| boolean     | ✓ | ✓ | x | x | 1 bit    |
| base64      | x | x | ✓ | ✓ | variable |
| int16BE     | x | x | ✓ | ✓ | 16 bit   |
| int16LE     | x | x | ✓ | ✓ | 16 bit   |
| int32BE     | x | x | ✓ | ✓ | 32 bit   |
| int32LE     | x | x | ✓ | ✓ | 32 bit   |
| uint16BE    | x | x | ✓ | ✓ | 16 bit   |
| uint16LE    | x | x | ✓ | ✓ | 16 bit   |
| uint32BE    | x | x | ✓ | ✓ | 32 bit   |
| uint32LE    | x | x | ✓ | ✓ | 32 bit   |
| floatBE     | x | x | ✓ | ✓ | 32 bit   |
| floatLE     | x | x | ✓ | ✓ | 32 bit   |
| doubleBE    | x | x | ✓ | ✓ | 64 bit   |
| doubleLE    | x | x | ✓ | ✓ | 64 bit   |
| bigUInt64BE | x | x | ✓ | ✓ | 64 bit   |
| bigUInt64LE | x | x | ✓ | ✓ | 64 bit   |

If the payload is smaller than the required bits for the conversion (payload.length < dataType.length), an error is displayed in the logs and no message is sent over MQTT. If the payload has more bits (payload.length > dataType.length) than needed for the conversion, the extra bits are ignored and a message is sent over MQTT.

As a comparison to other documentation, this is a list of other common names for the supported types:

| Common type name | Size   | Minimum value | Maximum value |
| ---------------- | ------ | ------------- | ------------- |
| char             | 8 bit  | 0             | 255           |
| byte             | 8 bit  | -128          | 127           |
| short (int16)    | 16 bit | -2^15         | 2^15-1        |
| int (int32)      | 32 bit | -2^31         | 2^31-1        |
| uint (uint32)    | 32 bit | 0             | 2^32-1        |
| long64           | 64 bit | -2^63         | 2^63-1        |
| float            | 32 bit | IEEE 754      | IEEE 754      |
| double           | 64 bit | IEEE 754      | IEEE 754      |

## Input Format

This Modbus implementation supports writing using the standard function codes 5, 6, 15 and 16. In most cases you can directly send a number in the message payload when you are trying to write to a coil or a single register (function codes 5 or 6, respectively).

When trying to write several coils at once (function code 15) your data message's `value` must consist of an array of boolean values, for example: `[true, true, false, true]`.

Alternatively, if your goal is to write several registers at once, the data type of the endpoint needs to be considered. The property `dataType` (see [Endpoint properties](https://docs.cybus.io/1-11-0/services/service-commissioning-files/resources/cybus-endpoint#properties)) specifies how to properly serialize the data into an array of bytes suitable to write into the Modbus registers.

For the available integer and float data types (see [Supported Data Types](#supported-data-types) above) you can directly send the value in the message payload. A `BigInt` must be sent as a string value. You can also send base64 and utf8 encoded strings that will be parsed using Node.js Buffer class.

Raw data in the form of an array of bytes is also supported.

### Input Format on Write

For writing data to Modbus, a message needs to be published to the `/set` topic of the endpoint with the following properties:

{% code lineNumbers="true" %}

```yaml
{ 'fc': '<function code value>', 'dataType': '<one of the Modbus data types>', 'data': '<the data to be written>' }
```

{% endcode %}

### Output Format on Write

Results are published to the `/res` topic of the endpoint. The format depends on the Modbus function being called and it is returned as a JSON object.

## Output Format

If data is read from Modbus and `dataType` is set to any of the supported values

### Output Format on Read

When data is read from the endpoint, results are published to the `/res` topic of the endpoint. The output message is an object with two properties:

{% code lineNumbers="true" %}

```yaml
{ 'timestamp': '<unix timestamp in ms>', 'value': '<value>' }
```

{% endcode %}

The value of the `value` property will be the JSON representation of the configured `dataType`, i.e. a number, or a string, or for raw the JSON representation of a JavaScript buffer object.

Alternatively, the property `dataType` can be left undefined, in which case the output is a JavaScript buffer object directly. This is probably useful for further processing using suitable [mappings](https://docs.cybus.io/1-11-0/documentation/services/service-commissioning-files/resources/cybus-mapping).

## Service Commissioning File Example

The following example demonstrates how to configure a simple Modbus connection and endpoint that reads holding registers (FC 3) from the device.

{% file src="<https://3526354945-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FrCPVzPlizXFgeCsIL7jH%2Fuploads%2Fgit-blob-a8b09ab5b4238a623890ecc0616f95be977b51d2%2Fmodbus-example.yml?alt=media>" %}

{% code title="modbus-example.yml" lineNumbers="true" %}

```yaml
# ----------------------------------------------------------------------------#
# Commissioning File
# ----------------------------------------------------------------------------#
# Copyright: Cybus GmbH (2020)
# Contact: support@cybus.io
# ----------------------------------------------------------------------------#
# Source Interface Definition - Modbus TCP
# ----------------------------------------------------------------------------#

description: |
    Sample commissioning file for Modbus TCP protocol connectivity and data mapping

metadata:
    name: ModBus TCP Protocol Connectivity
    icon: https://www.cybus.io/wp-content/uploads/2019/03/Cybus-logo-Claim-lang.svg
    provider: cybus
    homepage: https://www.cybus.io
    version: 0.0.1

parameters:
    IP_Address:
        type: string
        default: 192.168.10.30

    Port_Number:
        type: number
        default: 502

    initialReconnectDelay:
        type: integer
        default: 1000

    maxReconnectDelay:
        type: integer
        default: 30000

    factorReconnectDelay:
        type: integer
        default: 2

resources:
    modbusConnection:
        type: Cybus::Connection
        properties:
            protocol: Modbus
            targetState: connected
            connection:
                host: !ref IP_Address
                port: !ref Port_Number
                connectionStrategy:
                    initialDelay: !ref initialReconnectDelay
                    maxDelay: !ref maxReconnectDelay
                    incrementFactor: !ref factorReconnectDelay

    readCoil:
        type: Cybus::Endpoint
        properties:
            protocol: Modbus
            connection: !ref modbusConnection
            subscribe:
                fc: 1
                length: 2
                interval: 1000
                address: 3
                dataType: boolean

    writeCoil:
        type: Cybus::Endpoint
        properties:
            protocol: Modbus
            connection: !ref modbusConnection
            write:
                fc: 5
                length: 2
                address: 3
                dataType: boolean

    readRegister:
        type: Cybus::Endpoint
        properties:
            protocol: Modbus
            connection: !ref modbusConnection
            subscribe:
                fc: 3
                length: 2
                interval: 1000
                address: 1
                dataType: int16BE

    writeRegister:
        type: Cybus::Endpoint
        properties:
            protocol: Modbus
            connection: !ref modbusConnection
            write:
                fc: 6
                length: 2
                address: 1
                dataType: int16BE

    mapping:
        type: Cybus::Mapping
        properties:
            mappings:
                - subscribe:
                      endpoint: !ref readCoil
                  publish:
                      topic: !sub '${Cybus::MqttRoot}/read/coil'
                - subscribe:
                      topic: !sub '${Cybus::MqttRoot}/write/coil'
                  publish:
                      endpoint: !ref writeCoil
                - subscribe:
                      endpoint: !ref readRegister
                  publish:
                      topic: !sub '${Cybus::MqttRoot}/read/register'
                - subscribe:
                      topic: !sub '${Cybus::MqttRoot}/write/register'
                  publish:
                      endpoint: !ref writeRegister
```

{% endcode %}
