Siemens SIMATIC S7
Connect to Siemens SIMATIC S7 PLCs using S7 Communication Services.
The SIMATIC S7 is a product line of PLCs (S7-200, S7-300, S7-400, S7-1200, S7-1500) by Siemens widely used in industrial automation. S7 PLCs connect multiple sensors and actuators through digital or analog I/Os with modular extension capabilities.
S7 PLCs are configured and programmed using STEP 7 (TIA Portal) software from Siemens.
Read and write access to PLC data is realized through S7 Communication Services based on ISO-on-TCP (RFC1006). The PLC acts as a server, allowing communication partners to access PLC data without requiring connection configuration during PLC programming.
Activating PUT/GET Access
To activate S7 Communication Services, enable PUT/GET access in the PLC settings. This allows other applications to access the controller.

Configuring the Connection
Hardware-Specific Values
S7-300
0
2
S7-400
See hardware configuration
-
WinAC
See hardware configuration
-
S7-1200
0
1
S7-1500
0
1
Address Structure
The address of a PLC variable is a string with the following structure:
<data block number>,<memory area><data type><byte offset>.<bit position>.<array length>
<data block number>
Name of the data block where the value is stored (e.g., DB10). Only use this parameter if your value is part of a data block.
<memory area>
Memory area where the value is stored.
input
I
peripheral input
PI
output
Q
peripheral output
PQ
marker
M
counter
C
timer
T
<data type>
Data type of the addressed value. The string data type can only be used in data blocks.
bit
X (or empty)
byte
B
char
C
word
W
int16
I
dword
DW
int32
DI
real
R
int64
LI (S7-1200/1500 only)
lreal
LR (S7-1200/1500 only)
string
S (only in data blocks)
date_and_time
DT
date_and_time in UTC
DTZ
date_and_time (12 byte)
DTL (S7-1200/1500 only)
date_and_time in UTC (12 byte)
DTLZ (S7-1200/1500 only)
<byte offset>
The byte offset to address.
<bit position>
Specifies the bit position when addressing individual bits. For string data types, this parameter defines the string length.
<array length>
Defines the array length when addressing multiple consecutive values.
The minimum required address information is <data block number> or <memory area>, <data type>, and <byte offset>. Use <bit position> only when addressing individual bits. <array length> is always optional.
Address examples
MR4 // REAL starting at marker byte 4 (MD4 in STEP 7)
M32.2 // Bit at marker byte 32 bit 2
PIW30 // WORD starting at peripheral input byte 30
PII30 // INT starting at peripheral input byte 30
DB1,R0.20 // Array of 20 REAL values in DB1 starting at byte 0
DB1,R4 // Single REAL value
DB1,REAL8 // Another single REAL value
DB1,I12.2 // Two INT value array
DB10,INT6 // DB10.DBW6 as INT
DB10,I6 // same as above
DB10,I6.2 // DB10.DBW6 and DB10.DBW8 in an array with length 2
DB10,S20.30 // String at offset 20 with length of 30 (actual array length 32 due to format of String type, length byte will be read/written)
DB10,S20.30.3 // Array of 3 strings at offset 20, each with length of 30 (actual array length 32 due to format of String type, length byte will be read/written)
DB10,C22.30 // Character array at offset 22 with length of 30 (best to not use this with strings as length byte is ignored)
DB10,X6.0.1 // Bit at DB10.DBX6.0 as array with length 1
DB10,DT0 // Date and time
DB10,DTZ0 // Date and time in UTC

Service Commissioning File Example
Output Format on Write
When data is written to an S7 endpoint, the result is published to the /res topic in the following format:
Output Format on Read
When data is read from a Siemens SIMATIC S7, the output is provided as a JSON object with the S7 data in the value property and the reception timestamp in the timestamp property.
Input Format on Write
When writing data to a Siemens SIMATIC S7, provide it as a JSON object with the S7 data in the value property:
Optionally, include an id property in the published message to use as a correlation value for the write operation response.
The write operation result is published on the /res topic for the endpoint. For more details on write operations, see Operation Results.