For the complete documentation index, see llms.txt. This page is also available as Markdown.

Modbus/TCP

Configure Connectware to read from and write to Modbus/TCP devices.

Modbus/TCP is a communication protocol that is a variant of the Modbus family. It is based on a client/server architecture and intended for use in industrial automation, especially with PLCs or I/O modules. Modbus/TCP is defined in IEC 61158.

Modbus uses big-endian byte order for addresses and data items.

Protocol Structure

Each Modbus/TCP frame consists of the following fields:

Transaction identifier
Protocol identifier
Length field
Unit identifier
Function code
Data

2 byte

2 byte (always 0x0000)

2 byte (n+2)

1 byte

1 byte

n byte

For configuration reference, see:

Supported Function Codes

For reading or writing data over Modbus/TCP, the protocol provides a set of functions. Which action should be performed on the other end of the connection is defined by the function code (FC).

The following function codes are supported:

Function code
Action
Operation

1

Read coils

read, subscribe

2

Read discrete inputs

read, subscribe

3

Read holding registers

read, subscribe

4

Read input registers

read, subscribe

5

Write single coil

write

6

Write single holding register

write

15

Write multiple coils

write

16

Write multiple holding registers

write

Supported Data Types

In Modbus/TCP there are no predefined data types. Connectware supports sending the raw payload over MQTT as binary. If the data type is known and supported by the respective function code, the payload is converted to JSON format.

The desired data type on read or on write is specified with the property dataType. The possible values are as follows:

DataType/FC
1
2
3
4
Size

raw

✓

✓

✓

✓

variable

boolean

✓

✓

x

x

1 bit

base64

x

x

✓

✓

variable

int16BE

x

x

✓

✓

16 bit

int16LE

x

x

✓

✓

16 bit

int32BE

x

x

✓

✓

32 bit

int32LE

x

x

✓

✓

32 bit

uint16BE

x

x

✓

✓

16 bit

uint16LE

x

x

✓

✓

16 bit

uint32BE

x

x

✓

✓

32 bit

uint32LE

x

x

✓

✓

32 bit

floatBE

x

x

✓

✓

32 bit

floatLE

x

x

✓

✓

32 bit

floatBEWS

x

x

✓

✓

32 bit

floatLEWS

x

x

✓

✓

32 bit

doubleBE

x

x

✓

✓

64 bit

doubleLE

x

x

✓

✓

64 bit

The floatBEWS and floatLEWS types apply the same conversion as floatBE and floatLE, but swap the two 16-bit words before reading or writing the value. Use them for devices that store 32-bit floats in word-swapped register order.

If the payload is smaller than the required bits for the conversion (payload.length < dataType.length), an error is displayed in the logs and no message is sent over MQTT. If the payload has more bits (payload.length > dataType.length) than needed for the conversion, the extra bits are ignored and a message is sent over MQTT.

The following table maps Connectware data types to common names used in other documentation:

Common type name
Size
Minimum value
Maximum value

char

8 bit

0

255

byte

8 bit

-128

127

short (int16)

16 bit

-2^15

2^15-1

int (int32)

32 bit

-2^31

2^31-1

uint (uint32)

32 bit

0

2^32-1

long64

64 bit

-2^63

2^63-1

float

32 bit

IEEE 754

IEEE 754

double

64 bit

IEEE 754

IEEE 754

Input Format

This Modbus implementation supports writing using the standard function codes 5, 6, 15 and 16. In most cases you can directly send a number in the message payload when you are trying to write to a coil or a single register (function codes 5 or 6, respectively).

When trying to write several coils at once (function code 15), the message itself must be an array of boolean values, for example: [true, true, false, true].

Alternatively, if your goal is to write several registers at once, the data type of the endpoint needs to be considered. The property dataType (see Endpoint Properties) specifies how to properly serialize the data into an array of bytes suitable to write into the Modbus registers.

For the available integer and float data types (see Supported Data Types above) you can directly send the value in the message payload. A BigInt must be sent as a string value. You can also send base64 and utf8 encoded strings that will be parsed using the Node.js Buffer class.

Raw data in the form of an array of bytes is also supported.

Input Format on Write

To write data to Modbus, publish the value itself to the /set topic of the endpoint. The function code (fc) and dataType come from the endpoint configuration, so the message contains no other properties. For example, to write the number 42:

To write several coils with function code 15, publish an array of boolean values:

Output Format on Write

Connectware publishes the result on the /res topic of the endpoint. The result is a JSON object with details of the Modbus request and the response of the device. Its content depends on the function code.

Output Format

Output Format on Read

If dataType is set, a read endpoint publishes the result on its /res topic and a subscribe endpoint publishes on the endpoint topic. The message is an object with timestamp, in milliseconds since the Unix epoch, and value:

value is the JSON representation of the configured dataType, that is, a number, a string, or for raw the JSON representation of a JavaScript buffer object.

Alternatively, the property dataType can be left undefined, in which case the output is a JavaScript buffer object directly. With batch read processing enabled, interval-based subscribe endpoints publish an object with timestamp and value instead. The buffer output is useful for further processing using suitable mappings.

Batch Read Processing

By default, Connectware reads each Modbus endpoint individually, sending one request per endpoint to the device. In deployments with many endpoints, this can result in slow read cycles, especially when the device or network introduces even small delays with each request.

Batch read processing improves this by combining multiple read requests into a single, larger one wherever possible. Connectware automatically identifies which endpoints can be batched — those sharing the same unit ID and function code with addresses close enough to fit within a single read range. This reduces the total number of requests per cycle and can significantly shorten read times for large configurations.

No changes to endpoint definitions are required when enabling batch read processing. Connectware automatically determines which endpoints can be grouped based on their address, unit ID, and function code.

Endpoints configured with a cron schedule are not included in the batch scan cycle. They continue to poll individually as usual.

Enabling Batch Read Processing

Enable batch processing by setting batchReadEnabled and maxBatchSize on the Modbus connection resource. For more information, see Connection Properties.

Example

The following example enables batch processing on a Modbus connection:

Service Commissioning File Example

The following example demonstrates how to configure a simple Modbus connection and endpoint that reads holding registers (FC 3) from the device.

Last updated

Was this helpful?