OPC UA Server

This page describes how Connectware can act as an OPC UA server. Connectware can also act as a OPC UA client.

To run an OPC UA server, the commissioning file must contain a server resource of type Cybus::Server::Opcua. This will start an OPC UA server that can be accessed by OPC UA clients. From the OPC UA client, this server is reachable by the following address:

opc.tcp://<connectwareHost>:4841<resourcePath>

If your Connectware instance is running on a system that is reachable by a DNS hostname, this hostname must be specified in the hostname property, so that the server is reachable from outside of the Connectware docker network. The value localhost is not valid in this case, as localhost refers to the local Docker container but not the host itself, which means this name is not reachable from other containers or the host system.

Additionally, the property resourcePath is important when when connecting to the OPC UA server. This property defines the prefix of the connection string and defaults to the value /UA/CybusOpcuaServer. Please note that this string has to be added to the URL when connecting from a client to the OPC UA Server. Otherwise the client might not be able to connect successfully.

The server configuration is specified by the properties of the server resource. The actual data points (nodes in OPC UA) are specified by defining resources of type Cybus::Node::Opcua, one resource for each node. The nodes are structured in a tree-like hierarchy. There must be exactly one root node, which has its parent property set as a reference to the server object. All other nodes reference either the root node or other intermediate nodes as parent, forming a tree of nodes on the OPC UA Server.

Nodes can be defined within the same service as the OPC UA server, or also in other services using inter-service referencing using the service-id. It is thus possible to add or remove nodes while the OPC UA server is running, by adding more service commissioning files.

Security Settings

For production use, the connection to the OPC UA server should only be established using the security profile SignAndEncrypt. Any other security profile bears the risk that the communication between client and server can easily get manipulated or compromised. Per default, the built-in OPC UA server only allows connections with SignAndEncrypt security setting enabled (in the property securityModes). Please use your Connectware credentials when authenticating to the OPC UA server by Connectware username and password user token.

Custom Server Properties

Custom Node Properties

Service Commissioning File Example

Output Format

If the server receives data from an external OPC UA client, the output on the internal MQTT broker will be provided as JSON object:

Input Format

If the server should provide data to an external OPC UA client, the message on the internal MQTT broker must be published in this format:

Note: If 64-bit integers are being used (which are unsupported in JSON, but are supported in Javascript by the BigInt class), the value must be given as a string that contains the decimal number.

OPC UA Method Implementation

OPC UA methods can only be implemented on servers when used in conjunction with FlowSync.

When configured in transaction mode, Cybus::Nodes handle operations differently than standard variable nodes. Any node with the setting operation: transaction follows this workflow:

  1. Publishes request data to the /treq topic.

  2. Waits to receive a response on the /tres topic before proceeding.

Example

The following example configuration is taken from FlowSync Example 6

Request Data Structure

When a method is called, it publishes request details to the /treq topic in the following format:

  • Each request contains a unique id for tracking.

  • The response must include this same id to complete the flow.

This approach ensures proper request-response pairing and flow completion.

Example

The data structure matches the format shown in FlowSync Example 6.

Response Data Format

Each method call must receive a corresponding response published to the /res topic.

Example

In the FlowSync Example 6, the response will look like this:

Error Response Format

To return an error response from a node, you must include an error property containing the appropriate error code. This code will be used in the method call response. Note that any error.message provided will be ignored.

Example